INPUT | |
Sensor Type | pt100 100 Ohm @ 0ºC 2 or 3 wire |
Sensor Range | (-200 to 850)ºC (18 to 390) Ohm |
Sensor Connection | Screw Terminal |
Minimum Span (See note 1) | 25ºC |
Linearisation | BS EN 60751 (IEC 751) Standard / JISC 1604 |
Accuracy (See note 2) | ±0.1ºC ±0.05% of Reading |
Thermo Drift | 0.0025% /ºC |
Excitation Current | <200μA |
Lead resistance effect | 20Ω per leg |
Maximum Lead Resistance | 0.002ºC/Ω |
Note 1 | Any span may be selected, full accuracy is only guaranteed for spans greater than the minimum recommended Span. |
Note 2 | Basic measurement accuracy includes the effects of calibration linearisation and repeatability. |
OUTPUT | |
Type | Two wire (4 to 20 mA) Sink |
Limits | Low 3.8mA; High 21.5mA |
Accuracy | ±0.1ºC ±0.05% of Reading |
Loop effects | ±0.2μA / V measured @ 50Hz 1 V (peak to peak) |
Thermal Drift | ±1μA/ºC Typical; ±1.5μA Max. |
Max Load | [(Vsupply-10)/20]KΩ |
DIN KOS203P Temperature Converter In-Head
The KOS203P in-head transmitter incorporates the latest digital technology to ensure accurate drift free linearisation. It connects to any standard RTD Temperature sensor and converts the output to a linear 4-20mA output signal, providing a level of performance at a cost that was not possible with early analogue types.
A simple push button operation ranges and calibrates the KOS203P 4-20mA temperature transmitter, eliminating the need for soldering links, potentiometers or PCB’s.
High accuracy and stability coupled with the flexibility of reduced stock holding and the quick and easy way of bench re-arranging makes the KOS203P the ideal choice for the majority of RTD sensing requirements.
The KOS203P is linearised to comply with all common RTD sensor standards without affecting accuracy as the Zero & SPAN are se to a particular sensor type.
An on board LED indicates the successful completion of the range programming and also provides an instant indication of sensor health.
Update Time | 0.5 Seconds |
Response Time | 1 second to reach 90% of the final value |
start up time | From power up typically 5 seconds |
Filter Factor | Adaptive |
Ambient Temperature | -40ºC to +85ºC |
Connection | Screw Terminal |
Approvals | BN EN 61326; 1998 - Electrical equipment for measurement and control ANNEX A; ANNEX F |
Factory Default | 0 to 100ºC upscale burnout (0.0ºC user trim) |